PROMGAZ
Address: Russia, 117420, Moscow, Nametkina str., 6
Phones: +7 (495) 504-42-70, 504-43-92; Fax: +7 (495) 504-43-70, 504-43-80
E-mail: promgaz@promgaz.ru , marketing@promgaz.ru
THE PRODUCTS MANUFACTURED:
ONE- STAGES GAS BURNERS PROMGAZ-1
TWO-STAGES GAS BURNERS PROMGAZ-2
MODULATING PROGRESSIVE TWO-STAGE GAS BURNERS PROMGAZ-M
SELF-CONTAINED MODULAR BOILER PLANTS
ONE- STAGES GAS BURNERS PROMGAZ-1
PG-1/0,03; PG-1/0,05; PG-1/0,09; PG-1/0,14; PG-1/0,23;
Specifications:
|
Values for burners PG-1/ |
0,03 |
0,05 |
0,09 |
0,14 |
0,23 |
|
Fuel |
Natural gas |
||||
|
Rated thermal power, kW |
34 |
58 |
93 |
140 |
232 |
|
Thermal power setting range, kW |
11,5 - 34,0 |
23,0 – 58,0 |
40,5 – 93,0 |
70,0 - 140,0 |
104,0 - 232,0 |
|
Associated pressure, not exceeding, kPa |
2,0 |
||||
|
Motor power, W |
50 |
75 |
75 |
110 |
200 |
|
Maximum absorber power, W |
160 |
215 |
223 |
250 |
300 |
|
Weight, not exceeding, kg |
13 |
14 |
18 |
20 |
21 |
|
Minimum excess-air factor for rated thermal power |
1,05-1,15 |
||||
|
Monophase electricity supply |
220 V, 50 Hz |
||||
TWO-STAGES GAS BURNERS PROMGAZ-2
PG-2/25; PG-2/40; PG-2/60; PG-2/70; PG-2/100; PG-2/150; PG-2/180; PG-2/250
Specifications:
|
Values for burners PG-2/ |
25 |
40 |
60 |
70 |
100 |
150 |
180 |
250 |
|
Fuel |
Natural gas |
|||||||
|
Thermal power setting range, MW |
0,07 - 0,23 |
0,08 - 0,35 |
0,10 - 0,52 |
0,13 - 0,75 |
0,20 - 1,16 |
0,28 - 1,75 |
0,35 - 2,20 |
0,38 - 2,90 |
|
Associated pressure, not exceeding, kPa |
2,0 |
2,0 |
2,0 |
2,2 - 3,1 |
2,5 - 3,7 |
3,2 - 3,8 |
4,2 - 11,0 |
6,2 - 8,8 |
|
Motor power, KW |
0,24 |
0,37 |
0,74 |
1,10 |
2,20 |
3,00 |
4,00 |
5,50 |
|
Maximum absorber power, KW |
0,45 |
0,63 |
0,95 |
1,15 |
2,30 |
3,40 |
4,50 |
6,00 |
|
Weight without fittings, not exceeding, kg |
44 |
44 |
44 |
140 |
140 |
140 |
140 |
140 |
|
Minimum excess-air factor for rated thermal power |
1,05-1,15 |
|||||||
|
Electricity supply |
220V, 50 Hz |
3-phase 380/220V, 50 Hz |
||||||
MODULATING PROGRESSIVE TWO-STAGE GAS BURNERS PROMGAZ-M
PG-M/70; PG-M/100; PG-M/150; PG-M/180; PG-M/250; PG-M/350; PG-M/450; PG-M/550
Specifications:
|
Values for burners PG-M/ |
70 |
100 |
150 |
180 |
250 |
350 |
450 |
550 |
|
Fuel |
Natural gas |
|||||||
|
Thermal power setting range, MW |
0,14 - 0,75 |
0,20 - 1,16 |
0,28 - 1,74 |
0,35 - 2,20 |
0,38 - 2,90 |
1,40 - 4,00 |
1,85 - 5,20 |
2,30 - 6,40 |
|
Associated pressure, not exceeding, kPa |
2,2 - 3,1 |
2,5 - 3,7 |
3,2 - 3,8 |
4,2 - 11,0 |
6,2 - 12,0 |
5,4 - 14,0 |
6,0 - 20,0 |
8,6 - 29,5 |
|
Motor power, KW |
1,1 |
2,2 |
3,0 |
4,0 |
5,5 |
9,2 |
11,0 |
15,0 |
|
Maximum absorber power, KW |
1,15 |
2,30 |
3,40 |
4,50 |
6,00 |
9,70 |
11,50 |
15,50 |
|
Weight without fittings, not exceeding, kg |
150 |
|||||||
|
Minimum excess-air factor for rated thermal power |
1,05 - 1,15 |
|||||||
|
Electricity supply |
3-phase 380/220V, 50 Hz |
|||||||
SELF-CONTAINED MODULAR BOILER PLANTS
Application:
The boilers are intended for hot-water supply of living, production, medical, sporting and other facilities. The boilers are featured with automatic operation regime and environmental safety.
Specifications:
|
Parameter |
AMК 100 |
АМК 200 |
АМК 300 |
АМК 400 |
АМК 500 |
АМК 750 |
АМК 1000 |
АМК 1250 |
АМК 1500 |
АМК 2000 |
АМК 2200 |
АМК 3300 |
|
Rated calorific power, kW |
100 |
200 |
300 |
400 |
500 |
750 |
1000 |
1250 |
1500 |
2000 |
2200 |
3300 |
|
Model of hot-water boiler (KVa, KVg) |
50 |
100 |
100 |
200 |
250 |
500
|
500 |
500
|
500 |
1000 |
1100 |
1100 |
|
Number of hot-water boilers |
2 |
2 |
3 (2x150) |
2 |
2 |
2 (3x250) |
2 |
3 |
3 |
2 |
2 |
3 |
|
Fuel |
Natural gas |
|||||||||||
|
Heated volume, m3, ceiling height 3 m |
3000 |
6000 |
9000 |
12000 |
15000 |
22500 |
30000 |
37500 |
45000 |
66000 |
66000 |
99000 |
|
Operating gas pressure, MPa (kg/cm2) |
0,0013 |
0,01 |
||||||||||
|
Gas flow rate, m3/h |
depends on the boiler |
|||||||||||
|
Efficiency, % |
90 |
|||||||||||
GAS-FIRED MIXING AIR HEATERS
The VGS gas-fired air heaters are designed for heating the air fed into ventilation systems, air heating systems, heated air screens, drying units and for other purposes. Heated air mixed with gas combustion products is supplied to users. Hazardous compounds' content in the heated air is lower than the permitted concentration. This is achieved through the optimization of design and aerodynamic characteristics of the air heaters, complete gas combustion, excessive air supply.
The weight of the air heaters with the efficiency of up to 99 % is 6 - 8 times lower than that of conventional heaters. The absence of such a heat carrier as water helps to sharply reduce maintenance and operation costs.
The air heaters are equipped with automation and control devices which maintain the heater operation in the pre-set mode and shut-down it in emergency. The VGS air heaters are significantly cheaper than typical heaters of the same heat power.
Specifications:
|
Type |
VGS - 0,15 |
VGS - 0,4 |
VGS - 0,7 |
VGS - 1,0 |
VGS - 1,6 |
VGS - 2,0 |
VGS - 2,6 |
VGS - 6,3 |
VGS - 0,7Т |
VGS - 1,0Т |
|
Rated heat power, MW |
0,15 |
0,4 |
0,7 |
1 |
1,6 |
2 |
2,6 |
6,3 |
0,7 |
1 |
|
Rated gas flow, m3/h |
15 |
40 |
70 |
100 |
160 |
200 |
260 |
630 |
70 |
100 |
|
Heated air flow, th m3/h |
7,5 |
20 |
34 |
50 |
74 |
90 |
100 |
250 |
10 |
10 |
|
Heat carrier inlet and outlet temperature difference, °C |
30-80 |
30-80 |
30-80 |
30-80 |
30-80 |
30-80 |
30-80 |
30-80 |
190 |
300 |
|
Inlet gas pressure, kPa |
Up to 30 |
|||||||||
|
Burner block weight, kg |
76 |
241 |
172 |
285 |
462 |
605 |
665 |
1845 |
494 |
600 |
GAS BOILER
Application:
Cast iron boiler equipped with atmospheric burner is designed for low pressure natural gas and propane-butane combustion. Two-sectional dimension-type is applicable to heat flats (apartments) and offices, small-sized living quarters and country houses. The boiler is manufactured as water heating unit with heating water forced circulation and 4 bar working pressure.
Advantages:
High durability of cast iron heat exchanger and other parts, efficiency factor of 90-92%; high quality protection and control devices ensure stability, safety and reliability of boiler unit; combustion products reverse motion (flyback) control automatics will initiate shutdown in case of flue duct draught insufficiency; noiseless operation mode; low content of noxious gases in combustion products; easy and quick to assemble, maintain and repair; if combustion products discharge ventilator is installed to exhaust directly through the wall, the boiler can be mounted in a room without flue duct.
Specifications:
|
Parameters |
Value |
|
Quantity of sections, item |
2 |
|
Nominal capacity, kW |
5-8
|
|
Weight, kg |
73 |
|
Boiler unit water volume, liter |
7 |
|
Diameter of exhaust flue duct, mm |
80 |
|
Boiler unit overall dimensions
|
|
|
Water working pressure, bar |
4 |
|
Heating water maximum temperature, °С |
85 |
|
Installation dimensions:
|
|
|
Power supply |
220V, 50Hz |
|
Power consumption, W |
100 |
MINI BOILER UNIT
Application:
Cast iron double pressure gas mini boiler unit is equipped with atmospheric burner. It is designed for low-pressure natural gas combustion. The mini boiler unit is applied to heat flats (apartments), offices, houses and other buildings. The mini boiler unit is designed for heating and hot water supply with heating water forced circulation.
Advantages:
High durability of cast iron heat exchanger and other parts, efficiency factor of 90-91%; high quality protection and control devices ensure stability, safety and reliability of mini boiler unit; combustion products reverse motion (flyback) control automatics will initiate shutdown in case of flue duct draught insufficiency; noiseless operation mode; low content of noxious gases in combustion products; easy and quick to assemble, maintain and repair.
Specifications:
|
Parameters |
Value |
|
Quantity of sections, item |
4 |
|
Nominal capacity, KW |
19-27 |
|
Weight, kg |
175 |
|
Mini boiler unit water volume, liter |
19 |
|
Diameter of exhaust flue duct, mm |
140 |
|
Mini boiler unit overall dimensions
|
|
|
Water working pressure, bar |
4 |
|
Heating water maximum temperature, °С |
85 |
|
Heating water temperature, °С |
60 |
|
Installation dimensions:
|
|
|
Power supply |
220V, 50 Hz |
|
Power consumption, W |
100 |